0 data management, continued, 3 general power supply alarms, continued – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual
Page 53

53
746-257-B5-001, Rev. A1 (11/2013)
6.2.3 General Power Supply Alarms, continued
Active Alarm
Alarm type
Alarm Category
Probable Cause of Alarm
Corrective action
Standby Disabled
INPUT OVER CURR /
INPUT CURRENT LIMIT
Minor
PWR
AC Input current exceeds threshold setting.
1. Reduce Output Load
2. Check Input Current Limit Setting
NO
SURGE MOV FAIL
Minor
PWR
The MOV board surge protection has failed and needs
to be replaced.
1. Replace MOV board
NO
ALPHADOC OPTION
Minor
PWR
I2C has failed between XM3-HP and DOC.
1. Check ribbon cable
2. Replace DOC
NO
INVERTER ENABLE
Minor
PWR
System controller has disabled the Inverter.
1. Check inverter
YES
CHARGER ENABLE
Minor
PWR
System controller has disabled the charger.
1. Check charger
NO
APP OPTION
Minor
PWR
I2C has failed between XM3-HP and APP.
1. Check ribbon cable
2. Replace APP
NO
INV EEPROM ERROR
Minor
PWR
There has been an error reading the EEProm on the
inverter board.
1. Replace inverter
NO
HW COMPATIBILITY
Minor
PWR
There is a hardware incompatiblity between the Main
micro board and the inverter board.
1. Check Micro Board
2. Check Inverter Brd
NO
PDB EEPROM ERROR
Minor
PWR
There has been an error reading the EEProm on the
PDB.
1. Replace power supply
NO
Table 6-6, Power Alarms: Classifications, Causes and Corrections, continued
6.0 Data Management, continued