beautypg.com

0 data management, continued, 1 the alpha mib structure, 3 the alpha mibs, continued – Alpha Technologies AlphaNet IDH4 for XM3-HP Series - Technical Manual User Manual

Page 57: Table 6-9, alpha mib structure

background image

57

746-257-B5-001, Rev. A1 (11/2013)

6.3

The Alpha MIBs, continued

6.3.1 The Alpha MIB Structure

Measurements and settings for the power supply, generator, batteries and transponder are

accessed using Simple Network Management Protocol (SNMP) through the Alpha Management

Information Base (MIB) files.
The Alpha MIB is defined within the enterprise branch of the MIB tree starting at 1.3.6.1.4.1.926

and is organized into the following branches:

6.0 Data Management, continued

Refer to

Section 10.0 MIB Parameters for further details regarding the Alpha MIBs.

Alpha CIB Tables – atiTables (1.3.6.1.4.1.926.1.2.1)

Power supply, generator, battery and transponder data and settings are located in the CIB Tables branch (atiCibTables). The tables are sorted into the

following categories:

1.

Discretes - XM3-HP major alarms & installed XM3-HP options.

2.

Analogs - Voltages, currents, frequencies, temperatures.

3.

Counters - Batteries per string, number of strings, XM3-HP Self Test schedule, device address, total run time and configuration settings.

4.

Version - Device version information.

Alpha Management – atiManagement (1.3.6.1.4.1.926.1.3)

Advanced transponder settings are located in the Alpha management branch (atiManagement) and the settings are split between SNMP and system-

related settings.

1.

SNMP Management – atiMgntSnmp (1.3.6.1.4.1.926.1.3.1)

SNMP Trap tables, SNMP access, Community Strings and SNMP Trap controls.

1.1

SNMP Trap Table - Table of SNMP trap addresses.

1.2

SNMP Access Table – Table of SNMP access addresses.

1.3

SNMP Access – Device accessibility via SNMPv1 & SNMPv2 (Dual-IP only).

1.4

CPE Mode – Enable/disable Dual IP and Static IP settings.

1.5

Community Strings – Get, set and trap community strings (Dual-IP only).

1.6

SNMP Trap controls – Trap on normal, send count, SNMP timeout.

2.

System Management – atiMgmtSys (1.3.6.1.4.1.926.1.3.2)

Download, Web server, SNTP server IP addresses, enclosure environmental controller, general controls (tamper polarity).

2.1

Download – Transponder Proprietary Configuration File settings.

2.2

System Access – Enable/disable Web Page

2.3

System Servers – Simple Network Time Protocol server (SNTP) IP address.

2.4

Temperature Manager – Battery heater mat or cooler settings.

2.5

Phone Home – IP address and timer settings.

2.6

General Controls – Tamper switch polarity and internal bus data size.

2.7

General Info – Base configuration of the device. i.e. IDH4x, IDH4 Series, IDH4L.

2.8

System IO – Configuration and status of Environmental Controller

2.9

Non-volatile Memory Defaults – Factory and custom defaults.

Alpha Product Platforms – atiProductPlatforms (1.3.6.1.4.1.926.1.4)

System power supply parameters are located the Alpha Product Platforms branch (atiProductPlatforms).

1.

Broadband UPS

System View – Self Test, alarms, scalars, and counters reported by the host device.

1.1

Selects – Start/stop and control of the System Control Manager.

1.2

Alarms – Status of major and minor alarm, Self Test, temperature probe and input power.

1.3

Scalars – Power supply input voltage, frequency and current. Battery voltage and temperature. Charger settings.

1.4

Counters – Self Test and inverter counters.

2.

System Logs – atiProductPlatforms (1.3.6.1.4.1.926.1.4.1.2)

2.1

Events Table

2.2

Config Table

2.3

Perform Table

3.

System Apps – atiProductPlatforms (1.3.6.1.4.1.926.1.4.1.3)

3.1

Power Supply Health

3.2

Battery Status

3.3

Utility Quality

Table 6-9, Alpha MIB Structure