Alarms and events
234
A
Breaker Close Command
Rejected Breaker Locked Out
Breaker is locked out, so CPU has rejected
the close command
• If breaker has a manual lockout, verify
that the lockout has been reset.
• If the breaker has a network interlock, the
control logic is likely causing the breaker
to reject the close command.
• Contact GE Post Sales Service (see
Attention IO Card Detection
Mismatch Found 0 of 1
CPU expected 1 digital I/O card, but detected
none
Contact GE Post Sales Service (see
).
Attention IO Card Detection
Mismatch Found 0 of 2
CPU expected 2 digital I/O cards, but
detected none
Contact GE Post Sales Service (see
).
Attention IO Card Detection
Mismatch Found 1 of 0
CPU expected no digital I/O cards, but
detected 1
Contact GE Post Sales Service (see
).
Attention IO Card Detection
Mismatch Found 1 of 2
CPU expected 2 digital I/O cards, but
detected 1
Contact GE Post Sales Service (see
).
Attention IO Card Detection
Mismatch Found 2 of 0
CPU expected no digital I/O cards, but
detected 2
Contact GE Post Sales Service (see
).
Attention IO Card Detection
Mismatch Found 2 of 1
CPU expected 1 digital I/O card, but detected
2
Contact GE Post Sales Service (see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips