Alarms and events
224
A
Protection Defaulted Invalid
Frame Rating
Messenger reports a frame rating value that
is not valid, protection settings set to values
that are safe for all frame sizes
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
).
Protection Defaulted Invalid CT
Rating
Messenger reports a CT rating value that is
not valid, protection settings set to values
that are safe for all frame sizes
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
).
Protection Defaulted Frame And
CT Mismatch
Messenger reports frame and CT ratings that
are inconsistent, protection settings set to
values that are safe for all frame sizes
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
).
Protection Defaulted Invalid
Rating Switch
Messenger reports a rating switch value that
is not valid, protection settings set to values
that are safe for all frame sizes
Contact GE Post Sales Service (see
).
Attention Check Switch Invald LT
Overcurrent Set
Messenger reports a long time overcurrent
protection pickup setting that is not valid
Contact GE Post Sales Service (see
).
Caution Enet Cable
Disconnected Messngr CPUA
Messenger reports that it has no ethernet
connection to CPU A
Check connection between CPU A and
switch, and the switch and the Messenger.
Caution Enet Cable
Disconnected Messngr CPUB
Messenger reports that it has no ethernet
connection to CPU B
Check connection between CPU B and
switch, and the switch and the Messenger.
Attention Messngr Synch
Disabld Bad Freq CPUA
Messenger has received an invalid system
frequency from CPU A and will not be able to
synchronize from it
Contact GE Post Sales Service (see
).
Attention Messngr Synch
Disabld Bad Freq CPUB
Messenger has received an invalid system
frequency from CPU B and will not be able to
synchronize from it
Contact GE Post Sales Service (see
).
Invalid Setting IOC Mult CPUA
Chng Rejected
Messenger has received an invalid IOC
pickup setting from CPU A and has rejected
the value
This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting IOC Change
Rejected” or “Invalid Setting IOC Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting IOC Mult CPUB
Chng Rejected
Messenger has received an invalid IOC
pickup setting from CPU B and has rejected
the value
This event is recorded by CPU A based on
status information sent to the Messenger by
CPU B. The Sequence of Events for CPU B
should have an “Invalid Setting IOC Change
Rejected” or “Invalid Setting IOC Pickup
Change Rejected” event. See the description
of those events for details.
Invalid Setting ST From CPUA
Change Rejected
Messenger has received an invalid short time
enable or disable setting from CPU A and has
rejected the value
This event is recorded by CPU B based on
status information sent to the Messenger by
CPU A. The Sequence of Events for CPU A
should have an “Invalid Setting ST Change
Rejected” or “Invalid Setting ST Pickup
Change Rejected” event. See the description
of those events for details.
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips