GE Industrial Solutions Entellisys System User Manual User Manual
Page 224

Alarms and events
224
A
Protection Defaulted Invalid 
Frame Rating
Messenger reports a frame rating value that 
is not valid, protection settings set to values 
that are safe for all frame sizes
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
).
Protection Defaulted Invalid CT 
Rating
Messenger reports a CT rating value that is 
not valid, protection settings set to values 
that are safe for all frame sizes
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
).
Protection Defaulted Frame And 
CT Mismatch
Messenger reports frame and CT ratings that 
are inconsistent, protection settings set to 
values that are safe for all frame sizes
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
).
Protection Defaulted Invalid 
Rating Switch
Messenger reports a rating switch value that 
is not valid, protection settings set to values 
that are safe for all frame sizes
Contact GE Post Sales Service (see
).
Attention Check Switch Invald LT 
Overcurrent Set
Messenger reports a long time overcurrent 
protection pickup setting that is not valid
Contact GE Post Sales Service (see
).
Caution Enet Cable 
Disconnected Messngr CPUA
Messenger reports that it has no ethernet 
connection to CPU A
Check connection between CPU A and 
switch, and the switch and the Messenger.
Caution Enet Cable 
Disconnected Messngr CPUB
Messenger reports that it has no ethernet 
connection to CPU B
Check connection between CPU B and 
switch, and the switch and the Messenger.
Attention Messngr Synch 
Disabld Bad Freq CPUA
Messenger has received an invalid system 
frequency from CPU A and will not be able to 
synchronize from it
Contact GE Post Sales Service (see
).
Attention Messngr Synch 
Disabld Bad Freq CPUB
Messenger has received an invalid system 
frequency from CPU B and will not be able to 
synchronize from it
Contact GE Post Sales Service (see
).
Invalid Setting IOC Mult CPUA 
Chng Rejected
Messenger has received an invalid IOC 
pickup setting from CPU A and has rejected 
the value
This event is recorded by CPU B based on 
status information sent to the Messenger by 
CPU A. The Sequence of Events for CPU A 
should have an “Invalid Setting IOC Change 
Rejected” or “Invalid Setting IOC Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting IOC Mult CPUB 
Chng Rejected
Messenger has received an invalid IOC 
pickup setting from CPU B and has rejected 
the value
This event is recorded by CPU A based on 
status information sent to the Messenger by 
CPU B. The Sequence of Events for CPU B 
should have an “Invalid Setting IOC Change 
Rejected” or “Invalid Setting IOC Pickup 
Change Rejected” event. See the description 
of those events for details.
Invalid Setting ST From CPUA 
Change Rejected
Messenger has received an invalid short time 
enable or disable setting from CPU A and has 
rejected the value
This event is recorded by CPU B based on 
status information sent to the Messenger by 
CPU A. The Sequence of Events for CPU A 
should have an “Invalid Setting ST Change 
Rejected” or “Invalid Setting ST Pickup 
Change Rejected” event. See the description 
of those events for details.
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips
