GE Industrial Solutions Entellisys System User Manual User Manual
Page 191

Sequence of events cause code cross reference index
191
A
H-0089
Attention: Control Power 1 Outage Detected On Battery Backup
H-008A
Attention: Control Power 1 Low Battery Detected Shutdown in 2 mins
H-008B
Control Power 1 Power Restored
H-0091
Setting File Updated for CPU[A/B]
H-0092
Can't Update Setting File for CPU[A/B]
H-0096
IP Address in CPUA Written As [n.n.n.n] From [n.n.n.n]
H-0097
IP Address in CPUB Written As [n.n.n.n] From [n.n.n.n]
H-0098
HMI is restarted for Periodic maintenance.
C-7C01
Upgrade Successful
C-7C02
Events Cleared By Command
C-7C03
CPU Reinitialized Issued
C-7C04
Date Time Updated
C-7C06
Attention Breaker Open Failed Shunt Trip
C-7C07
Attention Breaker Close Failed
C-7C08
CPU Firmware Download Started
C-7C09
CPU Firmware Download Complete
C-7C0A
Attention Breaker Trip Failed Shunt Trip
C-7C0B
Discrete IO Test Mode Initiated
C-7C0C
Pickup ST Overcurrent
C-7C0D
Dropout ST Overcurrent
C-7C0E
Discrete IO Test Mode Ended
C-7C0F
Upgrade Failure Option String Corrupt
C-7C10
Breaker Trip ST Overcurrent
C-7C11
Pickup LT Overcurrent
C-7C12
Dropout LT Overcurrent
C-7C13
Breaker Trip LT Overcurrent
C-7C14
Pickup Ground Fault
C-7C15
Dropout Ground Fault
Table A-1 Sequence of events cause code cross reference index
Cause
Event Text
Page