GE Industrial Solutions Entellisys System User Manual User Manual
Page 210

Alarms and events
210
A
Caution: Firmware Download 
Failed for [CPU A/B/Messngr]. 
Unable to Enable Flash Pgm 
Mode. Replace CPU
Contact GE Service for CPU replacement
Contact GE Post Sales Service (see
).
Caution: Firmware Download 
Failed for [CPU A/B/Messngr]. 
Cannot Erase Firmware.Replace 
CPU
Contact GE Service for CPU replacement
Contact GE Post Sales Service (see
).
Firmware Downloaded OK To 
[CPU A/B/Messngr]
Logged upon successful completion of a CPU 
firmware upgrade
Firmware Download Failed for 
[CPU A/B/Messngr]
Contact GE Service for CPU replacement
Contact GE Post Sales Service (see
).
Caution: Firmware Download to 
[CPU A/B/Messngr] Cannot be 
Verified
Contact GE Service for CPU replacement
Contact GE Post Sales Service (see
).
Attention: Flash File Error in [CPU 
A/B/Messngr]. Unable to disable 
Flash Pgm Mode.Replace CPU
Contact GE Service for CPU replacement
Contact GE Post Sales Service (see
).
Caution: Firmware Dwnld Failed. 
Err Reading Messnger Status for 
[Breaker(s)]
An error was detected in confirming the 
status of a Messenger prior to upgrading its 
firmware.
Contact GE Post Sales Service (see
).
Caution: Firmware Dwnld Failed. 
Err Reading Messnger Status 
during Switch for [Breaker(s)]
An error was detected in confirming the 
status of a Messenger after its firmware has 
been updated.
Contact GE Post Sales Service (see
).
Caution: Settings Update 
Failed.Retry will Occur in 30 
minutes
An attempt to update the local settings file 
was unsuccessful and a retry will be 
attempted in the specified time period.
If this error is repeated, Contact GE Post Sales 
Service (see 
).
Caution: IP Error X For IP 
Address [n.n.n.n]
The HMI encountered an error in establishing 
a TFTP session with a CPU.
Note: FTP Error X
An error has occurred during FTP protocol 
transfer with a CPU. Contact GE Service.
Contact GE Post Sales Service (see
).
Note: TFTP Error X
An error has occurred during TFTP protocol 
transfer with a CPU. Contact GE Service.
Contact GE Post Sales Service (see
).
HMI File [Name] Published OK
The HMI successfully updated the specified 
file in the CPU
HMI File [Name] Retrieved OK
The HMI successfully retrieved the specified 
file from the CPU
Caution: Error Publishing File 
[Name]. Retry
An error has occurred attempting to updated 
the specified file and a retry will be 
attempted
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips