GE Industrial Solutions Entellisys System User Manual User Manual
Page 223

Alarms and events description and system troubleshooting guide
223
A
Invalid Setting IOC Pickup 
Change Rejected
Attempt to change IOC pickup setting has 
been rejected
The value entered for the IOC pickup setting 
was inconsistent with the protection options 
and frame size configured at the 
Compartment ID. Select a value that is 
consistent with these parameters.
Invalid Setting GF Change 
Rejected
Attempt to enable or disable ground fault has 
been rejected
The setting entered for GF enable was 
inconsistent with the protection options 
configured at the Compartment ID. Verify 
that the protection options are correct.
Invalid Setting GF Pickup 
Change Rejected
Attempt to change the ground fault pickup 
setting has been rejected
The value entered for the GF pickup setting 
was inconsistent with the protection options 
and frame size configured at the 
Compartment ID. Select a value that is 
consistent with these parameters.
Invalid Setting ST Change 
Rejected
Attempt to enable or disable short time has 
been rejected
The setting entered for ST enable was 
inconsistent with the protection options 
configured at the Compartment ID. Verify 
that the protection options are correct.
Invalid Setting ST Pickup Change 
Rejected
Attempt to change the short time pickup 
setting has been rejected
The value entered for the ST pickup setting 
was inconsistent with the protection options 
and frame size configured at the 
Compartment ID. Select a value that is 
consistent with these parameters.
Messenger/Breaker Config Status
Caution Messngr Control Power 
1 Lost
Messenger reports that it has lost control 
power source 1
• Check LINE LED on UPS. If it is off, check
the main power switch on the UPS. If it is 
off, turn it on. Otherwise, check the 
control power fuse between the 
transformer and the UPS.
• If the LINE LED is on, check the ON LINE
LED. If it is off, see the UPS manual.
• Check UPS fuse.
• Contact GE Post Sales Service (see 
Caution Messngr Control Power 
2 Lost
Messenger reports that it has lost control 
power source 2
Same as control power 1 lost
Messngr Control Power 1 OK
Messenger reports that control power source 
1 is present
Messngr Control Power 2 OK
Messenger reports that control power source 
2 is present
Note Invalid Breaker Type
Messenger reports a breaker type other than 
ANSI
Compartment ID button has been 
misconfigured, contact GE Post Sales Service 
(see 
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips