GE Industrial Solutions Entellisys System User Manual User Manual
Page 223
Alarms and events description and system troubleshooting guide
223
A
Invalid Setting IOC Pickup
Change Rejected
Attempt to change IOC pickup setting has
been rejected
The value entered for the IOC pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.
Invalid Setting GF Change
Rejected
Attempt to enable or disable ground fault has
been rejected
The setting entered for GF enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.
Invalid Setting GF Pickup
Change Rejected
Attempt to change the ground fault pickup
setting has been rejected
The value entered for the GF pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.
Invalid Setting ST Change
Rejected
Attempt to enable or disable short time has
been rejected
The setting entered for ST enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.
Invalid Setting ST Pickup Change
Rejected
Attempt to change the short time pickup
setting has been rejected
The value entered for the ST pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.
Messenger/Breaker Config Status
Caution Messngr Control Power
1 Lost
Messenger reports that it has lost control
power source 1
• Check LINE LED on UPS. If it is off, check
the main power switch on the UPS. If it is
off, turn it on. Otherwise, check the
control power fuse between the
transformer and the UPS.
• If the LINE LED is on, check the ON LINE
LED. If it is off, see the UPS manual.
• Check UPS fuse.
• Contact GE Post Sales Service (see
Caution Messngr Control Power
2 Lost
Messenger reports that it has lost control
power source 2
Same as control power 1 lost
Messngr Control Power 1 OK
Messenger reports that control power source
1 is present
Messngr Control Power 2 OK
Messenger reports that control power source
2 is present
Note Invalid Breaker Type
Messenger reports a breaker type other than
ANSI
Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see
).
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips