GE Industrial Solutions Entellisys System User Manual User Manual
Page 216
Alarms and events
216
A
Relays - Frequency and Reverse Power
Alarm Pickup Reverse Power
Alarm only reverse power relay has entered
pickup
Alarm Reverse Power
Alarm only reverse power relay has operated
Alarm Dropout Reverse Power
Alarm only reverse power relay has dropped
out of pickup
Pickup Reverse Power
Reverse power relay has entered pickup
Breaker Trip Reverse Power
Reverse power relay has operated
Dropout Reverse Power
Reverse power relay has dropped out of
pickup
Alarm Pickup Underfrequency
Alarm only underfrequency relay has
entered pickup
Alarm Underfrequency
Alarm only underfrequency relay has
operated
Alarm Dropout Underfrequency
Alarm only underfrequency relay has
dropped out of pickup
Voltage Below Underfreq Alarm
Blocking Voltage
The voltages on all three phases have
dropped below the alarm only
underfrequency blocking voltage threshold.
Voltage Above Underfreq Alarm
Blocking Voltage
The voltage on at least one of the three
phases has exceeded the alarm only
underfrequency blocking voltage threshold.
Pickup Underfrequency
Underfrequency relay has entered pickup
Breaker Trip Underfrequency
Underfrequency relay has operated
Dropout Underfrequency
Underfrequency relay has dropped out of
pickup
Voltage Below Underfrequency
Blocking Voltage
The voltages on all three phases have
dropped below the underfrequency blocking
voltage threshold.
Voltage Above Underfrequency
Blocking Voltage
The voltage on at least one of the three
phases has exceeded the underfrequency
blocking voltage threshold.
Alarm Pickup Overfrequency
Alarm only overfrequency relay has entered
pickup
Alarm Overfrequency
Alarm only overfrequency relay has
operated
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips