GE Industrial Solutions Entellisys System User Manual User Manual
Page 221

Alarms and events description and system troubleshooting guide
221
A
Invalid Set MSGF Zone1…4 Alrm 
Pkup Min Used
Pickup setting 1 for alarm only multi source 
ground fault for zone 1…4 has been set to the 
minimum allowable (current setting is too 
low)
Check pickup setting for MSGF zone. Value 
can be set higher if desired.
Invalid MSGF Sum Zone1…2 
Pkup Chng Rejctd
Pickup setting for multi source ground fault 
for summation zone 1…2 is too low, change is 
rejected
Set pickup value above the minimum allowed 
(20% of the smallest CT rating in the zone); 
CPU sets value to minimum in this case.
Invalid MSGF Sum Zone1…2 Alrm 
Pkup Chng Rejctd
Pickup setting for alarm only multi source 
ground fault for summation zone 1…2 is too 
low, change is rejected
Set pickup value above the minimum allowed 
(20% of the smallest CT rating in the zone); 
CPU sets value to minimum in this case.
Invalid MSGF Sum Zone1…2 
Pkup Min Used
Pickup setting for multi source ground fault 
for summation zone 1…2 has been set to the 
minimum allowable (current setting is too 
low)
Check pickup setting for MSGF Summation 
zone. Value can be set higher if desired.
Invalid MSGF Sum Zone1…2 Alrm 
Pkup Min Used
Pickup setting 1 for alarm only multi source 
ground fault for summation zone 1…2 has 
been set to the minimum allowable (current 
setting is too low)
Check pickup setting for MSGF Summation 
zone. Value can be set higher if desired.
Relays – High Resistance GF
Pickup High Resistance GF
High resistance ground fault has entered 
pickup
Dropout High Resistance GF
High resistance ground fault has dropped out 
of pickup
Alarm High Resistance GF
High resistance ground fault alarm has 
operated
Invalid Settings HRGF Unable To 
Detect Phase
The product of the pickup current setting and 
the ground resistance setting is greater than 
the nominal phase voltage
Check pickup current and ground resistance 
settings.
Relays – Synch Check
Synch Check Control Enabled 
1…6
Synch check relay 1…6 has been enabled
Synch Check Control Disabled 
1…6
Synch check relay 1…6 has been disabled
Synch Check 1…6 Sources Not 
Synchronized
Messengers that are providing voltage 
information for synch check relay are not 
synchronized, so the CPU is unable to check 
for synchronization between voltage sources.
This should only happen on start-up, or when 
a Messenger is connected to the system (or 
rebooted). If it happens repeatedly during 
normal operation, contact GE Post Sales 
Service (see 
).
Synch Check 1…6 Sources Not 
Compatible
Voltage sources for synch check relay 1…6 
are not compatible; i.e., they have different 
PT configurations or ratings
• Verify that the Source Voltages for the
synch check relay are correct.
• Verify that the source voltages have the
correct PT configurations.
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips
