3 ups compartment – GE Industrial Solutions Entellisys System User Manual User Manual
Page 184

Control power and UPS configuration
184
15
15.3 UPS compartment
Each of the two incoming power lines from CPTs “A” and “B” connects directly to a 30 A fuse 
upon entering the UPS compartment (see Figure 15-1).
Figure 15-1 Control Power & UPS overview
The system uses two throwover devices to select and transfer between the two sources to 
provide power to the uninterruptible power supplies (UPSs). Each of the two lines serves as a 
preferred source for one throwover device. Devices transfer from their preferred source if its 
voltage drops below a specified level. Pickup and dropout voltages for the throwover devices are 
set at the factory to 85% and 90% of the line voltage, respectively.
The two outputs from the throwover system are fed into a pair of 3 kVA UPSs. The UPSs are of 
the on-line double-conversion type, with 120 Vac 50/60 Hz inputs and outputs. The UPSs protect 
the power to the Entellisys instrumentation and circuit breaker control circuits during normal 
operation, line disturbances, and complete control power source loss. The UPS system does not 
provide power to the main switchgear bus nor the motor operator accessory of electrically 
operated circuit breakers.
Each UPS output is split into two circuits: one for circuit breaker control circuits and the other for 
instrumentation. Each of these (four) UPS-protected control power circuits is then fused to 
provide protection for the downstream system. 20 A fuses protect the circuit breaker control 
circuits, while 10 A fuses protect those of the Entellisys instrumentation. This architecture 
protects the central Entellisys instrumentation in the event of an interruption in circuit breaker 
control power.
In non-split Entellisys systems, the control power devices described above are located in a 
single instrument compartment. In split systems, however, the two control power networks 
(A&B) and their devices are placed in separate compartments. Thus, one input power fuse, one 
UPS, one throwover device, and two output fuses are housed in each compartment.
CPT 1
CPT 2
30A Fuse
30A Fuse
83X
83X
UPS A
UPS B
20A Fuse
10A Fuse
20A Fuse
10A Fuse
Term Blk
Term Blk
Term Blk
Term Blk
Term Blk
Term Blk
Term Blk
ROOF
Stack A
ROOF
Stack B
ROOF
Stack X
INST.
COMPT.
Stack B
BREAKER
COMPARTMENT
Stack B
UPS COMPARTMENT
Stack A
Term Blk
CPU
COMPT
MAIN
BUS
