Alarms and events
232
A
Commands from HMI
CPU Reinitialized Issued
CPU is going to reboot, either because of a 
modbus command, or an internal issue.
The reason for the CPU reboot should be in 
the event log. It will be one of the following: 
CPU Reinitialize By Command, Note CPU 
Internal Error 1, Note CPU Internal Error 2, 
Note CPU Internal Error 3
CPU Reinitialize By Command
CPU rebooted by Modbus reset relay 
command
The reset relay command is issued after new 
firmware or a new option string is 
downloaded to the CPU.
Breaker Open Command 
Received
CPU received a command via modbus to 
open a breaker
Breaker Close Command 
Received
CPU received a command via modbus to 
close a breaker
Breaker Trip Command 
Received
CPU received a command via modbus to trip 
a breaker
Events Cleared By Command
CPU received (via modbus) and executed a 
command to clear its event log
Waveforms Cleared By 
Command
CPU received (via modbus) and executed a 
command to clear its waveform capture 
buffers
Waveform Capture Triggered By 
Command
CPU received (via modbus) and executed a 
command to trigger a waveform capture
Fault Report Triggered By 
Command
CPU received (via modbus) and executed a 
command to trigger a fault report
Date Time Updated
CPU date and time changed
Demand Log Cleared All By 
Command
CPU received (via modbus) and executed a 
command to reset the demand log for a 
single breaker
Demand Log Cleared By 
Command
CPU received (via modbus) and executed a 
command to reset the demand logs for all 
breakers
Demand Reset By Command
CPU received (via modbus) and executed a 
command to reset the demand values for a 
single breaker
Demand Reset All By Command CPU received (via modbus) and executed a
command to reset the demand values for all 
breakers
Table A-2 Sequence of events description and troubleshooting guide
Event
Description
Notes and Troubleshooting tips