beautypg.com

6 grounding methods, Installation and wiring – Toshiba T2N User Manual

Page 78

background image

4.Installation and Wiring

User’s manual

63

(1) Installation of a Conductive Panel.

When the mounting frame itself has good conductivity, and is not in

common use with the earths of other power systems, proceed as below.

Power supply module

Conductive panel
(mounting frame)

Screws in 4 locations
(unpainted)

FG connection (when not on the same panel)

Dedicated ground

When not on the
same frame as
the basic unit,
insulate the
installed portion
and connect
between FG
terminals, via the
shortest distance

When the mounting frame does not possess good conductivity, or when

the frameground is a power system earth or is an unstable ground, use

the insulated installation shown in (2).

NOTE

4.6

Grounding Methods