Internal operations – Toshiba T2N User Manual
Page 116
2.INTERNAL OPERATIONS
User’s manual
103
The transition conditions for each mode are shown below.
•
When power turns to ON
Operation mode
switch
RUN/stand-by
switch
(DIP SW.3)
mode transition factor
operation
mode after
transition
RUN
OFF(RUN)
power on
RUN
ON(Stand-by)
power on
HALT
HALT
power on
HALT
•
When operation mode switch is changed
mode before transition
operation mode
operation mode
switch
mode transition factor
operation
mode after
transition
HALT
HALT
mode switch
→
RUN/
P-RUN
RUN
RUN
mode switch
→
HALT
HALT
•
When command is executed by peripherals (it is available only in RUN position
of operation mode switch.)
mode before transition
operation mode
operation mode
switch
mode transition factor
operation
mode after
transition
RUN
command HALT
HALT
HALT
RUN
command RUN
RUN
RUN
command Force RUN
RUN-F
RUN
command DEBUG
D-HALT
RUN/RUN-F
RUN
command HOLD
HOLD
HOLD
RUN
command HOLD cancel
RUN/RUN-F
(to previous
mode)
D-HALT
RUN
Debug function
D-RUN
D-RUN
RUN
detection break point or
command Force Stop
D-STOP
RUN
Debug function
D-RUN
D-STOP
RUN
command D-HALT
D-HALT
ERROR
command ERROR RESET
HALT
In the above table, the symbol ‘
’ means that mode transition is performed
independing on switchs’ setting or previous operation mode.
Refer to 5.6 for details of bedug mode. The FLT LED of the T2N CPU
module is blinking in DEBUG mode.
NOTE