6.Troubleshooting
Error Message and Associated Information
CPU LED Display
Classification
Error Message
Information 1
Information 2
Information 3.
Related Special
Relays
RUN
FLT
Meaning of Error and Countermeasures
LP function error
Error code
Error data
S0004
S0015
A fault has been detected in the language
processor for (LP).
When the state does not change even on
starting up again, replace the CPU module.
LP execution timeout
S0004
S0015
The operation of the language processor
(LP) is not completed within the specified
time. When the state does not change even
on starting up again, replace the CPU
module.
Processing
Scan time over
Scan time
S0006
S0031
The scan time exceeds 200ms. Shorten the
scan time or use the “WDT” instruction
No END /IRET error
Program type -
Block No.
Address in block
S0006
S0030
No "END" instruction has been programmed
in the main program or the sub program, or
no "IRET" instruction as been programmed
in the interrupt program.
Insert the "END", or the "IRET" instruction.
Pair inst error
Program type -
Block No.
Address in block
S0006
S0030
There is a fault in the method of using
instruction combinations MCS/R and JCS/R.
Check that the MCS/R and JCS/R command
combinations are correct.
Operand
Program type-
Block No.
Address in block
S0006
S0030
There is a fault in the operand assignment
for the Coil instruction or the FUN
instruction. Check whether an input (X) is
allocated to an output operand.
Program
Invalid program
Program type -
Block No.
S0006
S0030
A fault has been detected in the program
control information.
After executing Memory Clear, reload the
program.