2 power supply module, System configuration 6, Prosec t2n – Toshiba T2N User Manual
Page 21
![background image](/manuals/211365/21/background.png)
1.System Configuration
6
PROSEC T2N
1.2
Power Supply Module
Power supply modules are mounted on the left -end slots of all units. There are
two types according to the power voltage. Select one as required.
Model
Power Voltage
Output Rating
Weight
TPS261**S
100 - 240Vac
(+10%/-15%)
EX10*MPS31
24Vdc
(+20%/-15%)
Internal 5V power supply : 2.5A (max.)
External power supply : 24V,+10%/-10%
0.5A (max.)
(Internal + external total 15W or less)
Approx.
300g
•
External 24Vdc Output Terminals
These terminals can be used to supply 24Vdc power to external devices such as
sensors or relay output modules. 24Vdc(
±
10%)-0.5A(max.)
•
Run Signal Output Terminals
When the T2N is in the operating mode(RUN), built-in contact is closed.
240Vac(+10%)/24Vdc(+20%)-2A(max.)
(Can also be used on expansion units)
•
Power Supply Terminals
Connect to the power supply line. (See 4.7 Wiring the power supply).
•
Line Filter Ground Terminal / Frame Ground Terminal
These are grounding terminals. (See 4.6 Grounding methods).
RUN
1. The maximum rated output of the power supply module is 15W, this includes the
internal 5Vdc and external 24Vdc output combined. Configure the system, referring to
the Module Current Consumption Table on the next page, so that the following equation
is satisfied.
15W
≥
5V
×
Total 5V current (max. 2.5A) + 24V
×
external 24V current (max. 0.5V)
2. Do not connect the external 24V supply terminals to the other power supply systems,
and do not run the wiring over long distances.
3. This power supply module is dedicated power supply for the T2N and T2E/T2/EX100.
Do not use it by itself for other purposes.
TOSHIBA
POWER
+
-
OUT
OUT
NC
NC
IN
24Vdc
L
N
LG
FG
Terminal block
eject levers
Power supply
terminals
Power LED
Line filter ground terminal
External 24Vdc
output terminals
Frame ground terminal
Run signal output
terminals
NOTE