beautypg.com

Specification, User’s manual 39 – Toshiba T2N User Manual

Page 54

background image

2.Specification

User’s manual 39

4000 (a)

3000

2000

1000

0

4 10

4000

3000

2000

1000

-1000

-2000

(b)

(c)

-10 - 5 0 1 5

A/D Conversion

Analog Value

Analog Value

±

10V

Data Format (Input occupies 4 words)

4-20mA/1-5V

10(V)

D = Digital value

A = Analog value

20(mA)

(a)

4-20mA range : D = 250 x A-1000

(b)

1-5V range : D = 1000 x A-1000

(c)

±

10V range : D = 200 x A

F E D C B A 9 8 7 6 5 4 3 2 1 0

B * * * D D D D D D D D D D D D

S :

Sign bit
0 = Positive
1 = Negative

D :

Data bit (11 bits)
- 2000 - 2000 (HF830 - H07D0)
2's complement if negative

D :

Data bit (12 bits)
0-4000 (H0000-H0FA0)

B :

External line abnormal detection bit
0 = Normal
1 = Abnormal
(Current input line open, or external power OFF)

* : Always 0

F E D C B A 9 8 7 6 5 4 3 2 1 0

S S S S S D D D D D D D D D D D

4-Channel Analog Input

(12-bit) (Continued)

1. In the voltage input specification, when there is an open-circuit

between the input terminals, the data bits do not become 0.


2. It is recommended that unused channels be shorted between

the input terminals.

NOTE

Digital Value

Digital Value