Troubleshooting, User ’s manual – Toshiba T2N User Manual
Page 104

6.Troubleshooting
User
’s manual
89
Error Message and Associated Information
CPU LED Display
Classification
Error Message
Information 1
Information 2
Information 3.
Related Special
Relays
RUN
FLT
Meaning of Error and Countermeasures
Jump target error
Program type -
Block No.
Address in block
Jump label No.
S0006
S0030
The “LBL” instruction for the label No.
designated by a “JUMP” instruction has not
been programmed in the same program
type.
Or a “LBL” instruction is programmed on a
point before by the “JUMP” instruction.
(Backward jump) Program the “LBL”
instruction in a regular position.
No sub entry
Program type -
Block No.
Address in block
Sub-routine No.
S0006
S0030
The “SUBR” instruction for the sub-routine
No. designated by a “CALL” instruction has
not been programmed. Program the “SUBR”
Instruction.
No RET error
Program type -
Block No.
Address in block
Sub-routine No.
S0006
S0030
No “RET” instruction has been programmed
in the sub-routine.
Program the “RET” instruction
Sub nesting err
Program type -
Block No.
Address in block
Sub-routine No.
S0006
S0030
Sub-routine nesting has exceeded 6 layers.
Alter the program so that sub-routine nesting
is 6 layers or less.
Program
Loop nesting error
Program type -
Block No.
Address in block
S0006
S0030
“FOR”, “NEXT” instruction nesting has
exceeded 6 layers.
Alter the program so that “FOR”, “NEXT”
instruction nesting is 6 layers or less.