beautypg.com

6 analog output module application precaution, 6 analog output module - application precautions, Application precautions for i/o modules – Toshiba T2N User Manual

Page 73

background image

3.Application Precautions for I/O Modules

58 PROSEC T2N

(1) Use a shielded twisted-pair cable for the analog output signal line, and wire

over the minimum distance. Carry out the grounding of the cable shield

on the load side. (1) in the drawing below is the basic.

Sometimes, operation is more stable if the wiring is as in (2) or (3).

Analog
output
module

Analog
output
module

Analog
output
module

(2) Sometimes the conversion values are unstable, depending on the voltage

state of the external 24Vdc power supply.

If the conversion result is not stable, make the external power supply for

analog use a dedicated power supply.

Use of the 24Vdc external supply power source of the T2N power supply

module is recommended.

(3) All intrinsically shielded cables are occasionally fitted with ferrite choke

adjacent to analog inputs/outputs, must have ground connections to

grounded metalwork within 5cm for applying to the EMC directive.

3.6

Analog Output Module

Application Precaution