User data, User's manual – Toshiba T2N User Manual
Page 180

3.User Data
User's manual
167
Special
Register
Name
Function
SW042
SW056
Reserved (for future use)
SW057
Communication port response
delay mode
The T2N sends back the response on the communication port after waiting for
specified time (value*10ms) in the computer link mode.
specified value range :0-30
SW058
SW067
Reserved (for future use)
Special Device
Name
Function
S0680
S0681
S0682
S0683
S0684
S0685
S0686
S0687
End text for Free ASCII mode
(trailing code)
Can be changed as the trailing code when in the Free ASCII mode
Initial value = 0DH
S0688
Two wired system mode
Can connect to two wired system when this flag is ON in the Free ASCll mode
S0689
FIS communication status
ON when communication is normal in the FIS mode.
S068A
FIS start up flag
The FIS mode is started up when this flag is set to ON.
S068B
FIS connection status
ON when the FIS connection is completed normally.
S068C
FIS operation mode flag
ON : default setting mode
OFF : user specified setting mode
S068D
Link partner‘s operation mode
ON when the link partner‘s operation mode is RUN in the data link mode.
S068E
Data link status
ON when communication is normal in the data link mode.
S068F
Free ASCII reset
The Free ASCII mode is reset when this flag is set to ON.
Special
Register
Name
Function
SW069
Reserved (for future use)
~
~