Troubleshooting, Prosec t2n – Toshiba T2N User Manual
Page 105

90
PROSEC
T2N
6.Troubleshooting
Error Message and Associated Information
CPU LED Display
Classification
Error Message
Information 1
Information 2
Information 3.
Related Special
Relays
RUN
FLT
Meaning of Error and Countermeasures
SFC step No. error
Program type -
Block No.
Step No.
S0006
S0030
Is there multiple use of step Nos. in the SFC
program, or do the steps No.
designated by the initial step and the end
step not agree?. Change the step Nos. or
check the step No. of the end step.
SFC marco No. err
Program type -
Block No.
Macro No.
S0006
S0030
There is multiple use of a macro No. Or the
same macro program is called in 2 or more
places. Change the macro Nos. Or arrange
for the macro
program to be called in only 1 place.
No SFC macro entry
Program type -
Block No.
Macro No.
S0006
S0030
The macro program of the macro No.
designated by a macro step has not been
programmed. Check whether the macro
program has been programmed, or whether
the macro program No. is not in error.
SFC jump label err
Program type -
Block No.
SFC jump label
No.
S0006
S0030
There is multiple use of an SFC jump label
No.Change the SFC jump label No.
No SFC jump label
Program type -
Block No.
SFC label No.
S0006
S0030
The SFC label instruction for a jump label
No. designated by an SFC jump instruction
has not been programmed.
Program the SFC label instruction.
Duplicate SFC No.
Program type -
Block No.
SFC program No.
S0006
S0030
There is multiple use of an SFC program No.
Change the SFC program No.
Program
Invalid SFC prog
Program type -
Block No.
S0006
S0030
The initial step/end step or end, or the
macro/macro end, do not correspond. Alter
the program so that the initial step/end step
or end, or the macro/ macro end correspond.