Kawasaki D Series Controller MPVDCONTV113E-3 User Manual
Page 114

TROUBLESHOOTING
1-111
August 9, 2005
D SERIES CONTROLLER
TROUBLESHOOTING AND COMPONENT REPLACEMENT
Ka a a
w s k
ERROR CODE E1154
Option SIO port is not installed.
Main causes include:
1. Optional communication port (1GS board) is not installed to the 1KA board.
2. Optional communication port (1GS board) is not recognized by the 1KA board.
⇒
Install the optional communication port (1GS board) onto the 1KA board.
⇒
Replace the 1KA board.
_____________________________________________________________________
ERROR CODE E1155
A/D converter is not installed.
A/D converter board (1FH) is not installed to the 1KA board.
⇒
Install the A/D converter board (1FH).
_____________________________________________________________________
ERROR CODE E1156
[ARM CONTROL BOARD] Processing time over.
AS software processing did not complete within normal time.
⇒
Reset the error.
⇒
If this error recurs, contact KRI customer service
.
_____________________________________________________________________