Sharp JW-20CM User Manual

Page 94

background image

8

·

56

03

(8)

Remove the connector on point
A, and turn ON the termination
resistance of the master station.

07

(8)

06

(8)

05

(8)

Master

station

04

(8)

B

D

7

OFF

A

C

Disconnection

• If the bus cable between the slave station 05

(8)

and 06

(8)

is disconnected in the following system.

State of an individual communication flag

D

01

(8)

02

(8)

D

0

OFF

6

5

Unstable

1

2

3

4

D

7

D

0

OFF

OFF

6

5

ON

1

2

3

4

D

7

D

0

6

5

1

2

3

4

As the communication possible stations
03

(8)

, 02

(8)

, 01

(8)

, and 04

(8)

are normal, the

state of communication monitoring flag is
as follows.

Connect the A connector, and
then remove the connector on
point B.

D

7

D

0

OFF

6

5

OFF

Unstable

OFF

OFF

Unstable

Countermeasure

Cause

Disconnection in the bus cable and the
branch cable between the station 05

(8)

and

06

(8)

, or contact failure of the connectors

Error on the slave station 06

(8)

Remove both the bus cable and
the branch cable connectors. After
that, shorten one of these
connectors and check conductivity
using a tester.

Exchange the slave module.

OFF

1

2

3

4

There is no normal station amoung
commiunicatable station 05, 06, 07

(8)

,

and 05

(8)

is unstable.

Remove the connector on point
C and make sure the B
connector is not connected.

D

7

D

0

6

5

OFF

ON

1

2

3

4

As the communication possible station
05

(8)

is normal, abnormal points exists

ahead of the point C.

Connect the C connector and
make sure the B connector is
not connected, and remove the
connector at the next point to
the point D.

The station 05

(8)

and 06

(8)

become

communication possible stations, but the
station 05

(8)

is unstable and the station

06

(8)

is turned to OFF, so the abnormal

states occur between the point C and the
point D.