beautypg.com

Sharp JW-20CM User Manual

Page 143

background image

9

·

45

From the previous page

Set the number of sending bytes of the master station relay link [DCM (decimal), word]

• Set in parameter addresses 005000 to 005001

(8)

.

005000

(8)

005001

(8)

Upper

Lower

• These top addresses should not overlap the register link area, or the flag area, or exceed the

setting range (0 to 256 bytes for each station, 256 bytes for all stations in total).

In case of setting 8 bytes: Using JW-13PG example for page 9·41

Display the contents of parameter addresses 005000 to
005001

(8)

Write 00008

(D)

after converting to decimal.

Screen display of JW-13PG

To the next page

04774 D 00000
04776 D 00000
I PARAM.
>05000 D 00008

to

Set the number of sending bytes of the slave station (01 to 77) relay link [DCM (decimal), word]

• Set the number of sending bytes in decimal on the parameter addresses 005002 to 005177

(8)

.

(set in each station, 2 bytes for each station).

These top addresses should not overlap the register link area, or the flag area, or exceed the

setting range (0 to 256 bytes for each station, 256 bytes for all stations in total).

Lower

Upper

005176

(8)

005177

(8)

Lower

Upper

005002

(8)

005003

(8)

to

(In case of setting 4 bytes for slave station 01, and set 8 bytes for slave station 02: Example of page

9·41)

Slave station 01

Write 00004

(D)

in parameter

addresses 005002 to 005003

(8)

.

Slave station 02

Write 00008

(D)

in parameter

addresses 005004 to 005005

(8)

.

Screen display of JW-13PG

Slave
station 01

(8)

Slave
station 77

(8)

05000 D 00008
05002 D 00004
I PARAM.
>05004 D 00008

Enter by decimal

Enter by decimal