(2) Data memory starting system

The data memory starting system is the system which starts the SEND/RECEIVE functions without

using exclusive instructions. Set the target station number, data memory address, etc. on the

specified data memory (communication information storage area).

You can increase the amount of data to be transferred in one SEND/RECEIVE operation using

multiple connected channels.

For cases using 1 channel alone, maximum 256 bytes

For cases using 2 connected channels, maximum 512 bytes

For cases using 3 connected channels, maximum 768 bytes

For cases using 4 connected channels, maximum 1024 bytes

Set these channel connections on the parameter (address 007700 to 007703

(8)

). (See page 9·27

and 48)

[Setting the contents in a communication information storage area]

In order to assign a communication information storage area (64 bytes), set the top address on the

parameter (address 007710 to 007713

(8)

).

V5

FLAGS

TIMER

TYPE

ST1

R_SL

ST2

n (L)

n (H)

ADR_A(L)

ADR_A(H)

SEG_A

Not used

ADR_B(L)

ADR_B(H)

SEG_B

Not used

0

+01
+02
+03
+04
+05
+06
+07
+10
+11
+12
+13
+14
+15

+16

+17

+20

+37

+40

+57

+60

+77

The contents of each area (16 bytes) in channel CH1 to CH3

are the same as the contents of CH0.