Sharp JW-20CM User Manual
Page 75
8
·
37
Write 81
(H)
Writing to the EEPROM of the JW-20CM, start operation
[HEX (hexadecimal), byte]
From the previous page
· Write “81
(H)
” into parameter address 003777
(8)
and write the set parameter contents into the
EEPROM of the JW-20CM. Then start the remote I/O operate.
· After starting operation, the setting value changes to “01
(H)
.”
Display the contents of address
003777
(8)
PC operation
Turning a master station PC to monitor or change mode (PC operation).
(Operation example of JW-13PG)
Screen display of JW-13PG
Monitor mode
Change mode
Setting
value
(H)
Contents
Stop operation of the remote I/O (initial value)
· Calculate BCC of parameter addresses 000000 to 003775
(8)
.
When normal, the remote I/O will start operation.
When abnormal, the module will output error code BE
(H)
.
Check the parameter contents
When normal, the module calculates BCC and writes the check sum
value into address 003776
(8)
.
When abnormal, it outputs a BF
(H)
error code.
Changes the value to 00
(H)
(stops the operation of the remote I/O), and
writes it into the EEPROM.
If a write error to the EEPROM occurs, it outputs a 30
(H)
error code and
keeps the value set to 80
(H)
.
Writing to the EEPROM of the JW-20CM, start operation
Check the parameter contents
When normal, the module calculates BCC and writes the check sum
value into address 003776
(8)
.
When abnormal, it outputs a BF
(H)
error code.
Changes the value to 01
(H)
(starts the operation of the remote I/O), and
writes it into the EEPROM.
If a write error to the EEPROM occurs, it outputs a 30
(H)
error code and
keeps the value set to 81
(H)
.
Writing to the EEPROM of the JW-20CM, start operation
Initialize setting values of parameter addresses 000000 to 003777
(8)
0 0
(H)
0 1
8 0
(H)
8 1
(H)
0 8
03775 HEX 00
03776 HEX 00
I PARAM.
>03777 HEX 01
(Operation example of JW-13PG)