Sharp JW-20CM User Manual
Page 226
13
·
25
Setting range for "S"
· Rising edge of the input signal (OFF to ON) [
3]
Operation conditions
Flag
[
4]
PC model name
W70H/100H
JW50/70/100, JW50H/70H/100H
Setting range
[
2]
0000 to 1566
b0000 to b1766
09000 to 09766
19000 to 19766
0000 to 1566
b0000 to b1766
09000 to 09766
29000 to E1766
Contents
No ZW/JW-20CM on the option board
Waiting for a data transfer from a ZW/
JW-20CM
Completed a data transfer from a ZW/
JW-20CM
None of the above.
Non-carry
07354
0
1
0
0
Error
07355
1
0
0
0
Carry
07356
0
0
1
0
Zero
07357
0
0
0
0
[
1] The description for this instruction is for the ZW/JW-20CM only. It is different from the contents
in the PC programming manual. The F-201 instruction can only be used for one ZW/JW-
20CM module.
[
2] Use 0732 to 0737 for special relays.
[
3] When the F-200 instruction is turned ON, the non carry (07354) will be kept ON until the data
transfer to the number 2 port memory is complete. Even if the JW-20CM receives data from
an other station using the F-200 instruction, it will remain inside the ZW/JW-20CM until the
F-201 input signal changes ON from OFF, and the following data sent by the F-200 instruction
will not be received. If the PC power is turned OFF, the data currently being received will be
turned OFF.
[
4] If the JW-20CM receives data using a continuous stream of F-200 instruction, the receive
completion flag D+10
(8)
may not turn OFF. In this case use both the receive completion flag
and the carry (07356) when programming.