4 command – Sharp JW-20CM User Manual
Page 172
10
·
4
10-4 Command
For communication format etc., see network module ZW-98CM/ZW-20AX etc. instruction manual of
host computer side.
Read out relay (1 point unit)
Function
Read out ON (01
(H)
)/OFF (00
(H)
) status of specified relay.
Command code
00
(H)
(MRL)
Writing mode assignment
No
Operation condition of PC
Unrelated
Assignable address
00000 to 15777
(8)
Set/reset relay (1 point unit)
Function
Set (01
(H)
)/reset (00
(H)
) the specified relay.
Command code
10
(H)
(SRR)
Writing mode assignment
No
Operation condition of PC
Unrelated
Assignable address
00000 to 15777
(8)
· "Writing mode assignment" is used to show whether writing to the PC memory has been enabled or
disabled.
0: Writing prohibited
1: Enable writing only to data memory
2: Enable writing all data.
No setting: Enable writing in any mode
Letters in brackets are
command name of BASIC
mode.
Letters in brackets are