7

·

5

The recommended connector types are used.

The connectors are securely locked.

The connectors are insulated by T jacket or L jacket.

The recommended coaxial cable type is used.

Curved radius of the coaxial cables are more than 45 mm.

No heavy load is on the coaxial cables.

The coaxial cable is not bundled with a power line cable.

(Away from power line cables more than 100 mm.)

Length of branch lines is shorter than 400 mm.

Total length of the cable is less than 1 km.

Settings of the termination resistance switch and the shield ground switch are as per

the drawings.

7-5 Wiring of cables at outside control panels

Do not bundle the coaxial cable (the trunk and branch lines) together with power cables, and

separate from power cables at least by 100 mm. Do not put the coaxial cable into a power line wired
duct. The best way is to put the communication line in an independent duct.

Be careful that the coaxial cable does not receive any load by laying under a heavy weight such as

other cables.

When other cables run in the same duct as the coaxial cable, run the coaxial cable on the top

position.

Do not run the coaxial cable outdoors as it may cause damage to the JW-20CM due to inductive

lightning or atmospheric charge during lightning.

7-6 Check after wiring

Check the items below after completion of wiring.