beautypg.com

Remarks – Sharp JW-20CM User Manual

Page 60

background image

8

·

22

Indicates in [ ] of each item mean as follows:

(Example) Stop remote I/O operation [HEX (hexadecimal), bytes]

This means to set “stop remote I/O operation” by hexadecimal and byte unit.

Turn “ON” the power of slave module

Connect support tools

· Connect a support tool with the slave module

JW-20RS and prepare the setting parameter.

JW-13PG/12PG

JW-50SP

JW-50PG, Z-100LP2S

• For operation of each support tool, see the instruction manual attached. The following describes

an example of JW-13PG’s key operation.

Stop operation of remote I/O

[HEX (hexadecimal), byte]

· Setting of the parameter is only available when the operation of the JW-20RS is stopped.

· Write “00

(H)

” to parameter address 003777

(8)

and stop operation of the JW-20RS.

(Operation example of JW-13PG)

Reference Function of JW-13PG

• key: Changeover unit of figures

HEX

(hexadecimal)

OCT (octal)

DCM

(decimal)

Bit pattern

• key: Byte display Changeover word display

· Please set

to

of 8·24 and after when using ZW-I/O or JW-I/O.

To the next page

D i s p l a y t h e c o n t e n t s o f
parameter address 007777 by
hexadecimal.

Screen display of JW-13PG

07775 HEX 00
07776 HEX 1F
I PARAM.
>07777 HEX 00

Write
00

(H)

.

Remarks

Parameter
setting

This manual is related to the following products: