beautypg.com

Sharp JW-20CM User Manual

Page 144

background image

9

·

46

to

From the previous page

Set the number of sending bytes of the master station register link [DCM (decimal), word]

• Set the number of sending bytes in decimal on the parameter addresses 005200 to 005201

(8)

.

• These top addresses should not overlap the relay link area or the flag area, or exceed the setting

value (0 to 2048 bytes for each station, 2048 bytes for all stations in total).

005200

(8)

005201

(8)

Lower

Upper

(In case of setting 16 bytes using JW-13PG: Example of page 9·41)

Write 00016

(D)

in decimal notation.

Display the contents of parameter addresses 005200 to

005201

(8)

Screen display of JW-13PG

Set the number of sending bytes of the slave station (01 to 77

(8)

) register link [DCM (decimal), word]

• Set the number of sending bytes in decimal on the parameter addresses 005202 to 005377

(8)

.

(set in each station, 2 bytes for each station).

These top addresses should not overlap the resister link area, or the flag area, or exceed the

setting range (0 to 2048 bytes for each station, 2048 bytes for all stations in total).

Lower

Upper

Lower

Upper

005376

(8)

005377

(8)

to

005202

(8)

005203

(8)

(In case of setting 8 bytes both for slave station 01 and 02: example of page 9·41)

Slave station 01

Write 00008

(D)

in parameter

addresses 005202 to 005203

(8)

.

Screen display of JW-13PG

Slave station 02

Write 00008(D) in parameter

addresses 005204 to 005205

(8)

.

To the next page

Slave
station 01

Slave
station 77

(8)

05174 D 00000
05176 D 00000
I PARAM.
>05200 D 00016

05200 D 00016
05202 D 00008
I PARAM.
>05204 D 00008

Enter by decimal

This manual is related to the following products: