Set the number of sending bytes of the master station register link [DCM (decimal), word]
• Set the number of sending bytes in decimal on the parameter addresses 005200 to 005201
(8)
.
• These top addresses should not overlap the relay link area or the flag area, or exceed the setting
value (0 to 2048 bytes for each station, 2048 bytes for all stations in total).
005200
(8)
005201
(8)
Lower
Upper
(In case of setting 16 bytes using JW-13PG: Example of page 9·41)
Write 00016
(D)
in decimal notation.
Display the contents of parameter addresses 005200 to
005201
(8)
Screen display of JW-13PG
Set the number of sending bytes of the slave station (01 to 77
(8)
) register link [DCM (decimal), word]
• Set the number of sending bytes in decimal on the parameter addresses 005202 to 005377
(8)
.
(set in each station, 2 bytes for each station).
These top addresses should not overlap the resister link area, or the flag area, or exceed the
setting range (0 to 2048 bytes for each station, 2048 bytes for all stations in total).
Lower
Upper
Lower
Upper
005376
(8)
005377
(8)
to
005202
(8)
005203
(8)
(In case of setting 8 bytes both for slave station 01 and 02: example of page 9·41)
Slave station 01
Write 00008
(D)
in parameter
addresses 005202 to 005203
(8)
.
Screen display of JW-13PG
Slave station 02
Write 00008(D) in parameter
addresses 005204 to 005205
(8)
.
To the next page
Slave
station 01
Slave
station 77
(8)
05174 D 00000
05176 D 00000
I PARAM.
>05200 D 00016
05200 D 00016
05202 D 00008
I PARAM.
>05204 D 00008
Enter by decimal