Sharp JW-20CM User Manual

Page 83

background image

8

·

45

Top register address

Enter top address of each special I/O module, which can be allocated up to 64 points per unit, at

file addresses 000000 to 017700

(8)

.

Ex.: Set a JW-2DA (8 data bytes and a top register address of 490000) installed in "slave station

number 01," "rack number 0," "slot number 2" and assigned as No. 1 (1st module) using the

JW-13PG.

7 6 5 4 3 2 1 0 0 0

Lower 2 digits are always 00.

Bit contents of the parameter address

000603

(8)

etc.

4th digit 3rd digit

2nd digit 1st digit

5th digit

1: Enter top register address

0: Do not enter top register address

Slave station 01

Slave station 02

Slave station 03

Remote I/O
master station

JW-2DA

Display the contents of
address 000600

(8)

After converting into
octal notation, write
station number 01

(8)

Write rack number 0 and slot number

2 at parameter address 000601

(8)

.

After converting it into decimal notation at parameter

address 000602

(8)

, write the number of bytes 8.

After converting the number into octal notation
at parameter address 000603

(8)

, write it at 300

(8)

.

Screen display of JW-13PG

00601 OCT 003
00602 OCT 010

I PARAM.
>00603 OCT 300

1 1 0 0 0 0 0 0 0 0

3

0

0

0

0

0 0

1

Parameter address 000603

(8)

Set

File address 10000

(8)

= Register address 49000