Initialize Serial Ports button to configure a new Remote Base Unit.
Reconnect the two-wire system. Run the Base # Test again.
Advanced Two-Wire is Not Operational
Test Process
In the System Diagnostics interface, click the Base/TwoWire tab, and then click
the Base # Test button (where the # represents the number of the Remote Base
Unit that you want to test).
Message
The system is capable of operating in Advanced Two-Wire Mode but is currently
operating in standard two-wire mode.
Possible Causes
A newer Remote Base Unit has been added to an older system. This is not an
operational error and the system will continue to operate normally. No action is
necessary.
There are older components configured into the system. In some cases, an
adapter can be added to make these older units compliant with the Advanced
Two-Wire Standard.
A defective device is causing excess current in one power phase. The device is
also likely to fail with over current errors. Troubleshoot this situation using the
techniques specified in the Over Current section below.
Troubleshooting
Disconnect each device one at a time and run the Base # Test until the system
operates in advanced two-wire mode.
Correct the device, connect it to the two-wire system and run the Base # Test
again.
Continue to add devices one device at a time, running the Base # Test after each
device, until the entire system is connected and operating in advanced two-wire
mode.
Over Current
Test Process
In the System Diagnostics interface, click the Base/TwoWire tab, and then click
the Base # Test button (where the # represents the number of the Remote Base
Unit that you want to test).
Message
Over Current on the Two-Wire
Over Current on Base Unit
Possible Causes
A remote device is connected improperly with reversed wires.
The two-wire red and white are shorted together.
Remote Base Unit failure.
Troubleshooting
Visually verify all Remote Base Unit connections. Run the Base # Test again.
Verify the Remote Base Unit by disconnecting the two-wire system from the
Remote Base Unit. Run the Base # Test again.
Reconnect the two-wire system to the Remote Base Unit.