A Specifications

Power Requirements

Table A-1. HP NetServer LC 2000/2000r Input Power

Input Voltage and Frequency

100-240 VAC

±

10%; 50/60 Hz

Maximum inrush current

8 AMPs peak (for 1 power supply) 120 VAC
or 32 AMPs peak (2 power supplies)

16 AMPs peak (for 1 power supply) 240 VAC
or 32 AMPs peak (2 power supplies)

Delayed action circuit breaker
recommended

North America: a 20 A minimum delayed action
circuit recommended for each 16 A power
distribution unit (PDU) that is connected to an HP
NetServer LC 2000/2000r.

Europe (single server in a rack): use a
16 A-minimum circuit with one IEC MCB
C-type breaker for each 16-Amp PDU.

Europe (multiple servers in a rack): use a
16-amp-minimum circuit with one IEC MCB
D-type breaker for each 16 A PDU.

NOTE

Some local codes do not allow 16-amp service for a 16-amp
device. Consult a qualified electrician or local regulatory
authority before beginning electrical site preparation.

Table A-2. HP NetServer LC 2000/2000r Power Ratings

AC Input
Voltages

Maximum Input
Power (VA)

Maximum Input
Power (W)

Maximum Operating
Current RMS (AMPS)

100 VAC

545

540

5.5

120 VAC

531

525

4.5

208 VAC

516

506

2.5

230/240 VAC

514

504

2.3