MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 94 of 316

ProSoft Technology, Inc.

February 25, 2011

8.3

Archive Types

The module supports two types of archives: hourly archives and daily archives:

Archive Type

Period

Period End

Number of 30-Word
Archives Stored Locally

Hourly

60 minutes (1 hour)

Set by End-of-Hour Minute parameter

48

Daily

1440 minutes (1 day)

Set by End-of-Day Minute parameter

35


The Period End parameters must be set using the AFC Manager (Site

Configuration). The default value is zero for both archive types which means that:
Daily Archives are generated every day at midnight (00:00)
Hourly Archives are generated every hour on the hour (1:00, 2:00, 3:00, 4:00)
For example, if the parameters are configured as follows:
End-of-day minute = 480
The daily archives would be created every day at 08:00.
End-of-hour minute = 30
The hourly archives would be created every hour at 1:30, 2:30, 3:30, 4:30, and

so on.