2.3.6 Downloading the Project to the Module
1 Click P
ROJECT
/
D
OWNLOAD
P
ROJECT
.
2 This action opens the Local Port Settings window. Enter the port parameters
to use, and then click D
ONE
.
3 During the download operation, the following progress window is displayed:
4 When the file transfer is complete, the following window is displayed:
Note: The virtual slave remapping data (page 74) is not downloaded during the procedure because
it requires a separate download operation.
Troubleshooting Tip: If the AFC Manager displays an "Illegal Data Value" message, it typically
indicates an invalid meter type or product group configuration. The module does not accept a
configuration file that attempts to change a meter type or product group for a meter that is currently
enabled. Disable all meters, change the meter types and product groups, and then enable the
meters again.