ProSoft Technology MVI56-AFC User Manual
Page 204
MVI56-AFC Backplane Communication
MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 204 of 316
ProSoft Technology, Inc.
February 25, 2011
Description
This block issues Meter Disable (28) or Meter Enable (29) signals to the meter
logic in the AFC. A signal is an instruction for the AFC to perform a function once.
Signals are latched in the AFC and remain pending until they are discharged.
The OFB data element must be loaded with the bits set to correspond to the
meters to be disabled or enabled. The AFC returns the data element with the
bitmap of the enabled meters.
To schedule a signal, the Processor should latch the appropriate bit in the output
signal word. To prevent the accidental reissuing of signals, the Processor should
clear to zero the output signal word immediately after writing it to the module.
Signals: Output Function Block OFB
Signals: Input Function Block IFB
Element
Attribute
Element
Attribute
0
Block ID - Function Code
0
Block ID - Function Code
1
Signal Bits
Bit #
Meter Signal Bits
0
Disable/Enable Meter 1
1
Disable/Enable Meter 2
2
Disable/Enable Meter 3
3
Disable/Enable Meter 4
4
Disable/Enable Meter 5
5
Disable/Enable Meter 6
6
Disable/Enable Meter 7
7
Disable/Enable Meter 8
8
Disable/Enable Meter 9
9
Disable/Enable Meter 10
10
Disable/Enable Meter 11
11
Disable/Enable Meter 12
12
Disable/Enable Meter 13
13
Disable/Enable Meter 14
14
Disable/Enable Meter 15
15
Disable/Enable Meter 16
1
Bitmap of enabled meters
Special Notes
If bit 9 (V) of the block ID element of the Input Function Block is 0, this
indicates that the action was performed and event logged, or no action was
required.
If bit 9 (V) of the block ID element of the Input Function Block is 1, this
indicates that the event log is full - action was not performed.
Note: Refer to Function Block Structure (page 168) for information on Bit 8 and 9 settings.