14.4.1 Information for Users of AFC Manager Versions Older Than
2.01.000
If you are using AFC Manager versions older than 2.01.000, you must set these
bits using the Modbus master interface in the AFC Manager. Please refer to the
AFC Manager User Manual for further information about the Modbus Master
interface feature.
Refer to the following words to configure the archive options directly to the
Modbus database:
Address
Description
8341
Meter 1 daily archive configuration word
8421
Meter 1 hourly archive configuration word
10341
Meter 2 daily archive configuration word
10421
Meter 2 hourly archive configuration word
12341
Meter 3 daily archive configuration word
12421
Meter 3 hourly archive configuration word
14341
Meter 4 daily archive configuration word
14421
Meter 4 hourly archive configuration word
16341
Meter 5 daily archive configuration word
16421
Meter 5 hourly archive configuration word
18341
Meter 6 daily archive configuration word
18421
Meter 6 hourly archive configuration word
20341
Meter 7 daily archive configuration word
20421
Meter 7 hourly archive configuration word
22341
Meter 8 daily archive configuration word
22421
Meter 8 hourly archive configuration word
Each archive configuration word has the following bitmap structure:
Bit
Description
0
Period select, hourly
1
Archive upon period end
2
Archive upon event
3
Reserved
4
Reset resettable accumulator 1 upon period end
5
Reset resettable accumulator 2 upon period end
6
Reset resettable accumulator 3 upon period end
7
Reset resettable accumulator 4 upon period end
8
Reset resettable accumulator 1 upon event
9
Reset resettable accumulator 2 upon event
10
Reset resettable accumulator 3 upon event
11
Reset resettable accumulator 4 upon event
12
Reserved
13
Reserved
14
Reserved
15
Reserved
Note: Bit 0 must be set only for the hourly archives.