MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 104 of 316

ProSoft Technology, Inc.

February 25, 2011

The Selected Archive is continuously maintained to be a copy of the archive

record having the age given in the corresponding "Archive Select" holding

register, as listed in the following table. This means that the Selected Archive

changes whenever either (a) the age in the Open Archive Select register is

changed or (b) when the posting of a new archive causes the ages of all archives

to be increased by 1.

Meter

Open Daily Archive
Select Address

Open Hourly Archive
Select Address

1

8300

8301

2

10300

10301

3

12300

12301

4

14300

14301

5

16300

16301

6

18300

18301

7

20300

20301

8

22300

22301

9

24300

24301

10

26300

26301

11

28300

28301

12

30300

30301

13

32300

32301

14

34300

34301

15

36300

36301

16

38300

38301

Note: Meters 9 through 16 are only available for the PTQ-AFC and MVI56-AFC modules.

Use the following procedure to retrieve extended archives:
1 Copy the archive age to the correct Open Archive Select register.
2 Read the archive data from the 60000-range input addresses.

Example
To read Meter 2 Hourly Archive Number 277:
1 Write a value of 277 to Modbus Holding Register 10301.
2 Read the archive record data starting at input register 60150.

Note: This procedure can also be used to retrieve regular archives.