Events

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 133 of 316

February 25, 2011

Setup Phase
This phase, which opens a download session, may be accomplished in one of

two ways:
The Detailed Method
Issue a Modbus write of two registers to offset 0 of the LDW, specifying function
Open Session (1) and the desired Session ID followed by the number of the

desired starting event.

The Quick Method
Issue a Modbus write of a single register to offset 0 of the LDW, specifying

function Open Session (1) and the desired Session ID. This is equivalent to the

Detailed method in which the starting event is copied from the download pointer

in the event log header.
The dynamic context for the session includes two event numbers: one is the
Session Download Pointer (SDP), which is the number of the first event to be

retrieved by the next F&A cycle, and the other is the File Download Pointer

(FDP), which is the number of the earliest event on file that has not yet been

downloaded. The Setup phase specifies, explicitly or implicitly, the SDP, and

initializes the FDP from the download pointer in the event log header, so the SDP

and FDP need not be the same number.

Download Phase
This phase performs the actual retrieval of logged events as a sequence of F&A

cycles. All transactions must place the Session ID into the first register of data

(writes), or into the "number of registers" field of the Modbus command packet

(reads), as described in Section 5.

Fetch Transaction
Issue a Modbus holding-register read (function 3) addressed to offset 0 of the

LDW and with length calculated as (4+n*8), where n is the number of events to

be read and must lie between 0 and 14 inclusive; any other length constitutes an

error. Note that a read of 0 events is permitted, so that the LDW header can be

inspected without changing the session’s dynamic context; however, such a fetch

must still be acknowledged in the manner described next. The response is a

block of the requested length formatted as described in Section 6, whose second

register at offset 1 is the current value of the SDP.