MVI56-AFC Backplane Communication

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 160 of 316

ProSoft Technology, Inc.

February 25, 2011

11.1 MVI56-AFC Module Data Transfer

11.1.1 Input/Output Blocks for Data Transfer

When you configure the MVI56-AFC module to the I/O configuration of your

ControlLogix controller, the tags of the Output Block Array (OBA) and the Input

Block Array (IBA) for the module are automatically created as controller tags by

the RSLogix5000 programming software.

Output Block Array

Size: 248 elements

Data type: Integer (2 bytes)


The OBA is used for transferring process variables from individual meter runs

and other data that are available in the ControlLogix processor memory to your

AFC module via the backplane. This array is made up of a block of 248

contiguous integer elements.

Element

Attribute

Local 3.O (slot number)

Local.O.Data[0]

Local.O.Data[1]

Local.O.Data[2]

………………..

Local.O.Data[n]

………………..

Local.O.Data[247]


The meter run process variables such as temperature, pressure, differential

pressure, meter pulses, and so on. may come from other I/O modules in the rack

or from other sources like an HMI and so on. These variables must be copied to

predefined structured function blocks which transfer them to the AFC module as

part of one or more OBAs.