Master meter incompatible

configuration

For a master meter prover, both the line meter and
the master meter must be compatibly configured,

including identical settings of:

System of measurement units (US, SI)

Liquid density units (kg/m3, Rd/60, °API)

Product group

Measured quantity (gross volume pulses)

Reference conditions (base temperature and

pressure)

API calculation options (selection of density,

temperature, and pressure corrections)

For product group 8, Special applications, the

coefficient of thermal expansion Alpha

38

Master meter in calibration

The master meter has at least one process input in
calibration mode. Ensure that all process inputs are
live before attempting to use the master meter for
proving.

39

Master meter not enabled

The master meter is not enabled.

51

Invalid prover parameter

For a traditional (non-master-meter) prover, the base

prover volume (register 65036) must be greater than
zero, and, if the prover is single-walled, the inside

diameter, wall thickness, and modulus of elasticity

(registers 65038, 65040, and 65042) must all be

greater than zero.

52

Invalid prover controls

Some undefined bits in the at-enable controls

(register 65306 bits 0 through 7) have been set.