Meter Proving
MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 62 of 316
ProSoft Technology, Inc.
February 25, 2011
33
Master meter incompatible
configuration
For a master meter prover, both the line meter and
the master meter must be compatibly configured,
including identical settings of:
System of measurement units (US, SI)
Liquid density units (kg/m3, Rd/60, °API)
Product group
Measured quantity (gross volume pulses)
Reference conditions (base temperature and
pressure)
API calculation options (selection of density,
temperature, and pressure corrections)
For product group 8, Special applications, the
coefficient of thermal expansion Alpha
38
Master meter in calibration
The master meter has at least one process input in
calibration mode. Ensure that all process inputs are
live before attempting to use the master meter for
proving.
39
Master meter not enabled
The master meter is not enabled.
51
Invalid prover parameter
For a traditional (non-master-meter) prover, the base
prover volume (register 65036) must be greater than
zero, and, if the prover is single-walled, the inside
diameter, wall thickness, and modulus of elasticity
(registers 65038, 65040, and 65042) must all be
greater than zero.
52
Invalid prover controls
Some undefined bits in the at-enable controls
(register 65306 bits 0 through 7) have been set.