4 pulse (linear) meter with gas product, 5 orifice (differential) meter with liquid product – ProSoft Technology MVI56-AFC User Manual
Page 289
MVI56-AFC ♦ ControlLogix Platform
Reference
Liquid and Gas Flow Computer
User Manual
ProSoft Technology, Inc.
Page 289 of 316
February 25, 2011
14.5.4 Pulse (Linear) Meter with Gas Product
Start Offset
End Offset
Data Format
Type
Description
10
11
Accumulator
Snapshot
Accumulator totalizer, net
12
13
Floating point
Snapshot
Accumulator residue, net
14
15
Floating point
Flow weighted
average
Flow rate, net
16
17
Floating point
Flow weighted
average
Temperature
18
19
Floating point
Flow weighted
average
Pressure
20
21
Floating point
Flow weighted
average
K-Factor
22
23
Floating point
Flow weighted
average
Meter Factor
24
Word
Flow weighted
average
Relative density, e-4
25
Word
Flow weighted
average
Compressibility, reference, e-4
26
Word
Flow weighted
average
Compressibility, flowing, e-4
27
Word
Flow weighted
average
Supercompressibility, e-4
28
29
Double Word
Snapshot
Pulse Count
14.5.5 Orifice (Differential) Meter with Liquid Product
Start Offset
End Offset
Data Format
Type
Description
10
11
Accumulator
Snapshot
Accumulator totalizer, net
12
13
Floating point
Snapshot
Accumulator residue, net
14
15
Floating point
Flow weighted average
Flow rate, net
16
17
Floating point
Flow weighted average
Temperature
18
19
Floating point
Flow weighted average
Pressure
20
21
Floating point
Flow weighted average
Differential pressure
22
23
Floating point
Flow weighted average
Density input
24
Word
Flow weighted average
Corrected density (scaled integer)
25
Word
Flow weighted average
CTL e-4
26
Word
Flow weighted average
CPL e-4
27
Word
Flow weighted average
Velocity of approach factor, Ev, e-4
28
Word
Flow weighted average
Expansion factor, Y, e-4
29
Word
Flow weighted average
Coefficient of discharge, Cd, e-4