ProSoft Technology MVI56-AFC User Manual
Page 295
MVI56-AFC ♦ ControlLogix Platform
Reference
Liquid and Gas Flow Computer
User Manual
ProSoft Technology, Inc.
Page 295 of 316
February 25, 2011
Address
Type
Description
Ch00010 to Ch00015 Wd
Wallclock (Y,M,D,h,m,s)
The wallclock has a resolution of 1 second.
Ch00016 to Ch00017 Bm
Wallclock (packed)
The packed wallclock has a resolution of 2 seconds.
Ch00018
Bm
accessed port and authorization
bits 0- 3 - Accessed port; 0 = gateway
bit 4 - Password authorization waived for read
bit 5 - Password authorization waived for write
bit 6 - Password authorization granted for read
bit 7 - Password authorization granted for write
Ch00019
Wd
Password, read-enable
Ch00020 to Ch00089 --
[reserved]
Reserved for use by diagnostic and similar procedures.
Ch00090 to Ch00099 Wd
Arbitrary event-logged registers.
A Modbus master (such as the processor using Modbus Gateway) can use these to
record in the Event Log changes to values unrelated to flow measurement.