6 pulse (linear) meter with liquid product, 7 flow rate integration with gas product – ProSoft Technology MVI56-AFC User Manual
Page 290
Reference
MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 290 of 316
ProSoft Technology, Inc.
February 25, 2011
14.5.6 Pulse (Linear) Meter with Liquid Product
Start Offset
End Offset
Data Format
Type
Description
10
11
Accumulator
Snapshot
Accumulator totalizer, net
12
13
Floating point
Snapshot
Accumulator residue, net
14
15
Floating point
Flow weighted average
Flow rate, net
16
17
Floating point
Flow weighted average
Temperature
18
19
Floating point
Flow weighted average
Pressure
20
21
Floating point
Flow weighted average
K-Factor
22
23
Floating point
Flow weighted average
Meter Factor
24
25
Floating point
Flow weighted average
Density Input
26
Word
Flow weighted average
Water content, % e-2
27
Word
Flow weighted average
Corrected density (scaled integer)
28
Word
Flow weighted average
CTL e-4
29
Word
Flow weighted average
CPL e-4
14.5.7 Flow Rate Integration with Gas Product
Start Offset
End Offset
Data Format
Type
Description
10
11
Accumulator
Snapshot
Accumulator totalizer, net
12
13
Floating point
Snapshot
Accumulator residue, net
14
15
Floating point
Flow weighted average Flow rate, net
16
17
Floating point
Flow weighted average Temperature
18
19
Floating point
Flow weighted average Pressure
20
21
Floating point
Flow weighted average Flow Rate Input
22
Word
Flow weighted average Relative density, e-4
23
Word
Flow weighted average Compressibility, reference, e-4
24
Word
Flow weighted average Compressibility, flowing, e-4
25
Word
Flow weighted average Supercompressibility, e-4
26
Word
(available)
27
Word
(available)
28
Word
(available)
29
Word
(available)