ProSoft Technology MVI56-AFC User Manual
Page 110
Archives
MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 110 of 316
ProSoft Technology, Inc.
February 25, 2011
bit 4 Water content input out of range -
bit 5 Diff. pressure low -
bit 8 Orifice characterization error -
bit 9 Analysis total zero -
bit 10 Analysis total not normalized -
bit 11 AGA8 calculation error -
bit 12 API calculation error, density correctio -
bit 13 API calculation error, Ctl -
bit 14 API calculation error, vapor pressure -
bit 15 API calculation error, Cpl -
Status Bits
bit 11 Meter was enabled -
bit 12 Backplane communication fault -
bit 13 Measurement configuration changed -
bit 14 Power up -
bit 15 Cold start -
AFC-56(16) Daily Archive Date: 16-09-2002 16:26:44
Site Name: MVI Flow Station
Project: AFC
___________________________________________________________________________
Meter 1:
Tag M01
Archive 2
Closing timestamp of archive 2002-04-26.23:59:42
Opening timestamp of archive 2002-04-26.06:16:34
Status bitmap (details below) 60h
Alarms bitmap (details below) 0000h
Flowing period 1019877652
Event counter 53
Net accumulator (x f3) 174811
Net accumulator residue (x f3) 0,9399567
Net flow rate (x f3/h) 40247,88
Temperature (°F) 15,00736
Pressure (psig) 1000,416
Differential pressure (hw) 22,00479
Relative density (60°F/60°F) 0,7404
Reference compressibility 0,9989
Flowing compressibility 0,9053
Fpv 1,0506
Velocity of approach factor Ev 1,0331
Expansion factor Y 1,0001
Discharge coefficient 0,6045
Alarm Bits
bit 0 Temperature input out of range -
bit 1 Pressure input out of range -
bit 2 Diff. pressure input out of range -
bit 3 Flowing density input out of range -
bit 4 Water content input out of range -
bit 5 Diff. pressure low -