MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 102 of 316
ProSoft Technology, Inc.
February 25, 2011
8.8
Extended Archives
This feature is only supported on firmware versions 2.01.000 or newer, and
requires a Compact Flash card to be installed.
The module supports the extended archive feature that allows you to configure
more archives than the regular 35 daily archives and 48 hourly archives. The
module supports the following number of extended archives:
Daily Archives
Hourly Archives
Max Number of Archives
350 (version 2.04 and earlier)
1440 (version 2.05 and newer)
1260 (version 2.04 and earlier)
1440 (version 2.05 and newer)
Refer to Extended File Size entry on the Archive Configuration window for
more information.
Note: The maximum number of extended archives is not dependent on the number of words per
archive. Extended archives are stored on a Compact Flash card which must be installed for
Extended Archive configuration to be effective.
8.8.1 Retrieving Extended Archives
The module implements an easy way to retrieve extended archives from the
Modbus database. To learn how to retrieve extended archives, click Archive
Config on the Meter Configuration dialog box, and then click Modbus Addresses.
For each archive file the module reserves a block of 50 Input registers to hold the
"selected Archive", as listed in the following table.
Meter
Daily Archive Start
(Input Register)
Daily Archive End
(Input Register)
Hourly Archive Start
(Input Register)
Hourly Archive End
(Input Register)
1
60000
60049
60050
60099
2
60100
60149
60150
60199
3
60200
60249
60250
60299
4
60300
60349
60350
60399
5
60400
60449
60450
60499
6
60500
60549
60550
60599
7
60600
60649
60650
6069 9
8
60700
60749
60750
60799
9
60800
60849
60850
60899
10
60900
60949
60950
60999
11
61000
61049
61050
61099
12
61100
61149
61150
61199
13
61200
61249
61250
61299
14
61300
61349
61350
61399
15
61400
61449
61450
61499
16
61500
61549
61550
61599
Note: Meters 9 through 16 are only available for the PTQ-AFC and MVI56-AFC modules.