2 pre-defined header – ProSoft Technology MVI56-AFC User Manual
Page 287
MVI56-AFC ♦ ControlLogix Platform
Reference
Liquid and Gas Flow Computer
User Manual
ProSoft Technology, Inc.
Page 287 of 316
February 25, 2011
14.5.2 Pre-defined Header
These archive areas are included in the default archive data, and cannot be
reconfigured by the user.
Start
Offset
End
Offset
Data Format
Type
Description
0
1
Timestamp
Snapshot
Closing timestamp of archive
2
Word
Calculated
Flowing period
3
Bitmap
Calculated
Cumulative meter alarms
4
Bitmap
Calculated
Cumulative status
5
Word
Snapshot
Event counter
6
7
Double word
Calculated
Flowing period, seconds
8
9
Timestamp
snapshot
Opening timestamp of archive
Additional areas are also included in the default archive data, according to the
meter type and product group associated with the meter.
The cumulative meter alarms are defined as follows:
Offset
Description
0
Current archive, daily, cumulative meter alarm: Input out of range, temperature
1
Current archive, daily, cumulative meter alarm: Input out of range: pressure
2
Current archive, daily, cumulative meter alarm: Input out of range: differential
pressure
3
Current archive, daily, cumulative meter alarm: Input out of range: flowing density
4
Current archive, daily, cumulative meter alarm: Input out of range: water content
5
Current archive, daily, cumulative meter alarm: Differential Pressure Low
6
Current archive, daily, cumulative meter alarm: Orifice Pressure Exception
7
Current archive, daily, cumulative meter alarm: Accumulation overflow
8
Current archive, daily, cumulative meter alarm: Orifice characterization error
9
Not Used
10
Current archive, daily, cumulative meter alarm: Current archive, daily, cumulative
meter alarm: Analysis characterization error
11
Current archive, daily, cumulative meter alarm: Compressibility calculation error
12
Current archive, daily, cumulative meter alarm: Reference density error
13
Current archive, daily, cumulative meter alarm: Temperature correction error
14
Current archive, daily, cumulative meter alarm: Vapor pressure error
15
Current archive, daily, cumulative meter alarm: Pressure correction error