beautypg.com

ProSoft Technology MVI56-AFC User Manual

Page 189

background image

MVI56-AFC ♦ ControlLogix Platform

MVI56-AFC Backplane Communication

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 189 of 316

February 25, 2011

Word

Description

4

Analysis precision and stream assignment for meter 2

Bits

Contents

0, 1

Analysis slot number (0-based) for stream 1

2, 3

Analysis slot number (0-based) for stream 2

4, 5

Analysis slot number (0-based) for stream 3

6, 7

Analysis slot number (0-based) for stream 4



5

Analysis precision and stream assignment for meter 3

6

Analysis precision and stream assignment for meter 4

7

Analysis precision and stream assignment for meter 5

8

Analysis precision and stream assignment for meter 6

9

Analysis precision and stream assignment for meter 7

10

Analysis precision and stream assignment for meter 8

11

Analysis precision and stream assignment for meter 9

12

Analysis precision and stream assignment for meter 10

13

Analysis precision and stream assignment for meter 11

14

Analysis precision and stream assignment for meter 12

15

Analysis precision and stream assignment for meter 13

16

Analysis precision and stream assignment for meter 14

17

Analysis precision and stream assignment for meter 15

18

Analysis precision and stream assignment for meter 16

9 to 48

Zero


An application should not implement both 16-bit and 32-bit analysis blocks for the

same stream. The AFC will convert the analysis, whether 16-bit or 32-bit, to the

precision configured for the analysis slot assigned to the targeted stream, though

best practice would be to use the analysis block that matches the configured

precision.
The AFC clips component concentrations received in this block to the range

0.0000 through 6.5535, without raising a range alarm for any value that is

actually clipped. However, if clipping is performed then the analysis itself will

raise a normalization alarm.

This manual is related to the following products: