ProSoft Technology MVI56-AFC User Manual
Page 186
MVI56-AFC Backplane Communication
MVI56-AFC ♦ ControlLogix Platform
User Manual
Liquid and Gas Flow Computer
Page 186 of 316
ProSoft Technology, Inc.
February 25, 2011
Special Notes
Note 1: The address of each component will depend on which components are selected during the
configuration of the meter (using the AFC Manager). If less than 24 components are selected, they
are packed to remove unused component elements in the Analysis Block. The relative order of the
selected components is maintained and the overall size of the Analysis FB remains unchanged
(With firmware version 2.05 and later, you may choose to receive the analysis unpacked
regardless of the component selection; see the descriptions of Site Option bits 13 and 14 for more
information about the packing of analyses)
Note 2: The component mole fractions are entered as scaled integers. A component mole fraction
of .0753 (7.53 mole percent) is entered as the integer value 753. This number is internally divided
in the AFC module by 10,000.
Note 3: Refer to Function Block Structure (page 168) for information on Bit 8 and 9 settings.
11.2.7 Function Block Definition - 10: Meter Type Fetch
Note: This function is available only in versions 2.04 and later.
Output Function Block ID
Input Function Block ID
Function Block Name:
Meter Process Variables
Function Block ID:
10 decimal, 001010 binary, 10240 dec.
Target:
Selected Meter Number
Data Block Length:
1 Element
Total Block Length:
2 Elements