Orifice Meter with Gas Product
Meter PV: Output Function Block
Meter PV: Input Function Block
Element
Attribute
Element
Attribute
0
Block ID: Function Code &
Meter Number
0
Block ID: Function Code, Meter
Number, Active Stream Number
1
Reserved
1
Meter Alarms (Bitmap)
2
Temperature LS (see Note)
2
Net Accumulator LS (double
integer)
3
Temperature MS
3
Net Accumulator MS (double
integer)
4
Pressure LS (see Note)
4
Net Flow Rate LS (float)
5
Pressure MS
5
Net Flow Rate MS (float)
6
Differential Pressure LS (see
Note)
6
Gross Flow Rate LS (float)
7
Differential Pressure MS
7
Gross Flow Rate MS (float)
8
Reserved
8
Fpv LS (float)
9
Reserved
9
Fpv MS (float)
10
Reserved
10
Cprime LS (float)
11
Reserved
11
Cprime MS (float)
Pulse Meter with Gas Product
Meter PV: Output Function Block
Meter PV: Input Function Block
Element
Attribute
Element
Attribute
0
Block ID: Function Code &
Meter Number
0
Block ID: Function Code, Meter
Number, Active Stream Number
1
Reserved
1
Meter Alarms (Bitmap)
2
Temperature LS (see Note)
2
Net Accumulator LS (double
integer)
3
Temperature MS
3
Net Accumulator MS (double
integer)
4
Pressure LS (see Note)
4
Net Flow Rate LS (float)
5
Pressure MS
5
Net Flow Rate MS (float)
6
Meter Pulses LS (double
integer)
6
Gross Flow Rate LS (float)
7
Meter Pulses MS (double
integer)
7
Gross Flow Rate MS (float)
8
Reserved
8
Fpv LS (float)
9
Reserved
9
Fpv MS (float)
10
Meter Pulse Freq: Hz LS (float)
10
Cprime LS (float)
11
Meter Pulse Freq: Hz MS (float)
11
Cprime MS (float)